Loading…
Name ID Label Description Type Access Class
min_MBT_value 4029 Min SV Value Min value of Meter Body Temp. R Float 10
MBT_up_count 40A8 Time Above Upper Stress Limit Number of minutes Meter Body Temp. above upper stress limit R Unsigned 2050
MBT_down_count 40A9 Time Below Lower Stress Limit Number of minutes Meter Body Temp. below lower stress limit R Unsigned 2050
MBT_up_timestamp 40AA Time Since Last SV Up Time Since Last Event of Meter Body Temp. going to upper band R Unsigned 2048
MBT_down_timestamp 40AB Time Since Last SV Down Time Since Last Event of Meter Body Temp. going to lower band R Unsigned 2048
stress_life 40AC Comm Board Stress Life It gives the time duration for which the device has been under stress. Definition of Stress:It is the condition of the device in which any of the process variable/s exceed/s its stress limit/s. R Float 10
service_life 40AD Comm Board Service Life It gives the value of the device life already consumed. The consumption of device life depends uponthe 'Time in operation' and the 'Device Stress Life' parameters. More the value of these parameters moreis the life consumed. Device's life can be effectively used by ensuring lesser value of 'Device stress life' R Float 10
max_M360CoreT_value 40AE Max Sensor CPU Temp. Max value of sensor CPU core temperature R Float 10
min_M360CoreT_value 40AF Min Sensor CPU Temp. Min value of sensor CPU core temperature R Float 10
M360CoreT_up_count 40B0 Time Above Upper Stress Limit Number of minutes sensor CPU core temperature above upper stress limit R Unsigned 2050
Name ID Label Description Type Access Class