Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
detailed_status_0 | 4005 | DAC Failure | R/W | BitEnum | 2051 | |
detailed_status_1 | 4006 | Communication | R/W | BitEnum | 2051 | |
detailed_status_2 | 4007 | Display | R/W | BitEnum | 2051 | |
detailed_status_3 | 4008 | DAC Info | R/W | BitEnum | 2051 | |
detailed_status_4 | 4009 | Sensor | R/W | BitEnum | 2051 | |
detailed_status_5 | 400A | Sensor | R/W | BitEnum | 2051 | |
detailed_status_6 | 400B | Database Integrity | R/W | BitEnum | 2051 | |
detailed_status_7 | 400C | Display Integrity | R/W | BitEnum | 2051 | |
pressure_value | 138E | PV | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 10 |
pressure_upper_transducer_limit | 400D | UTL | UTL - Defines the highest acceptable value for the Transducer. UTL = 2*URL (Unit same as PV) if DP type UTL = 1.5*URL (Unit same as PV) if AP or GP type SPAN cannot be greater than UTL | R | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |