Loading…
Name ID Label Description Type Access Class
rPIDSetpoint1 40C5 PID Setpt Out 1 Sets the PID control setpoint for Output 1. R/W Float 0
rPIDSetpoint2 40C6 PID Setpt Out 2 Sets the PID control setpoint for Output 2. R/W Float 0
rPIDProportionalBand1 40C7 PID Prop Band Out 1 Sets the PID proportional band for Output 1. R/W Float 0
rPIDProportionalBand2 40C8 PID Prop Band Out 2 Sets the PID proportional band for Output 2. R/W Float 0
iOneLowUnsignedIntegerOutputIndexSC200 40CA R/W Index 4096
eErrorHoldMode 40CC Error Hold Mode Holds Outputs at last known value or switches to Transfer mode when sensor loses communication with controller. R/W Enum 64
eMeasurementSelect1 40CD Meas. Select Output 1 Selection list of sensor measurements. R Enum 64
eMeasurementSelect2 40CE Meas. Select Output 2 Selection list of sensor measurements. R Enum 64
eType1 40B6 Type Output 1 Selection list of output modes. R/W Enum 64
eType2 40B8 Type Output 2 Selection list of output modes. R/W Enum 64
iFilter1 4069 Filter Output 1 Time constant Output 1. R/W Unsigned 64
iFilter2 406A Filter Output 2 Time constant Output 2. R/W Unsigned 64
eMinCurrentSelect1 4067 0/4 mA Sel Out 1 Minimum current selection Output 1. R/W Enum 64
eMinCurrentSelect2 4068 0/4 mA Sel Out 2 Minimum current selection Output 2. R/W Enum 64
ePIDMode1 40C2 PID Mode Output 1 Auto/Manual mode selection for Output 1. R/W Enum 0
ePIDMode2 40C4 PID Mode Output 2 Auto/Manual mode selection for Output 2. R/W Enum 0
ePIDPhase1 40CF Phase Output 1 Direct/Reverse phase selection Output 1. R/W Enum 0
ePIDPhase2 40D0 Phase Output 2 Direct/Reverse phase selection Output 2. R/W Enum 0
iPIDIntegralTime1 40D1 PID Integral Out 1 Integral time in seconds Output 1. R/W Unsigned 0
iPIDIntegralTime2 40D2 PID Integral Out 2 Integral time in seconds Output 2. R/W Unsigned 0
iPIDDerivativeTime1 40D3 PID Derivative Out 1 Derivative time in seconds Output 1. R/W Unsigned 0
iPIDDerivativeTime2 40D4 PID Derivative Out 2 Derivative time in seconds Output 2. R/W Unsigned 0
iPIDTransitTime1 40D5 PID Transit Out 1 Stops all PID control for a selected period of time. R/W Unsigned 0
iPIDTransitTime2 40D6 PID Transit Out 2 Stops all PID control for a selected period of time. R/W Unsigned 0
eRange1 40D7 Range Output 1 Selection List of sensor ranges. R Enum 0
Name ID Label Description Type Access Class