Name ID Label Description Type Access Class
fSetSetPoint 40B9 Manual Setpoint Manual Setpoint- Manual valve setpoint in %. Value must be between -5.0% and +160.0%. W Float 4096
nSlotP 4045 P Proportional gain in %. Common values are 50 for small valves up to 4000 for large valves. Must be between 0 and 5000. R Unsigned 8
nSlotI 4046 I Integral time or reset time in 1/10 s. Higher values of I cause less integral action, however a value of 0 gives no integral action. Common values are 10 to 200. Values between 0 and 1000. R Unsigned 8
nSlotD 4047 D Derivative time or rate time in milliSeconds. Common values are 10 to 100. Values between 0 and 200. R Unsigned 8
nSlotPadj 4048 Padj Coefficient added to P when the valve is exhausting and compensates the variation in filling and exhausting speed. Can be positive or negative value range between -3000 to +3000. R Integer 8
nSlotBeta 4049 Beta Nonlinear gain factor. When beta is 0, the proportional gain is linear, otherwise the gain P is a function of error. The larger the beta, the smaller the gain for small error. Typical beta value is 7 or 8. Beta is ranging from -9 to +9. R Integer 8
nSlotPosComp 404B Position Comp. The response of the valve is different when the valve is nearly closed than when nearly open. This coefficient allows the user to make adjustments to try to equalize the valve response. Normal value is 6 and this value is ranging from 2 to 20. R Unsigned 8
nSlotDeadZone 404A Dead Zone When the valve position is within the setpoint +/- the dead zone and, no additional position control is performed. This value is normally 0%. Used to avoid limit cycling for high friction valves. Range is 0 to 5%. R Unsigned 8
nSlotDeadBand 404C Boost Boost- Compensates for the pnuematic dead band. Value ranges between 0 and 20. R Unsigned 8
nSlotNonLinear 40F3 Non Linear Non Linear R Unsigned 8
Name ID Label Description Type Access Class