Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
device_flags | 00A0 | Dev flags | Field Device Flags- Describes special features of the Field Device that affect the Data Link Layer | R | BitEnum | 2048 |
analog_channel_saturated1 | 103D | AO saturated | Field Device Specific Dynamic Variable Analog Output Saturated- Data that indicates which of the Analog Outputs are, or are not, saturated. The analog and digital Analog Outputs for the Dynamic Variable are beyond their limits and no longer represent the true applied process. | R | BitEnum | 2051 |
analog_channel_fixed1 | 1040 | AO fixed | Field Device Specific Dynamic Variable Analog Output Fixed- Data that indicates which of the Analog Outputs are, or are not, Fixed. The analog and digital Analog Outputs for the Dynamic Variable are held at a constant value (depending on the Mode of the Field Device). They will not respond to the applied process. | R | BitEnum | 2051 |
analog_channel_saturated_codes | 08D6 | R/W | Enum | 4096 | ||
analog_channel_fixed_codes | 08D7 | R/W | Enum | 4096 | ||
burst_mode_select | 0FFF | Burst mode | Burst Mode Select- Selects the mode for the Burst Mode functionality. If Burst is enabled the Field Device will generate HART messages on the Link without individual requests from the Host. | R/W | Enum | 128 |
loopCurrent | 00ED | Loop current | Corrente di loop - Valore della corrente di loop come percepito dal dispositivo. | R | Float | 66 |
loop_alarm_code | 00EC | AO Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 64 |
loop_flags | 00E7 | Channel flags | Analog Channel Flags- Defines the characteristics of the Analog Channel | R | BitEnum | 64 |
percentRange | 00E9 | PV % rnge | Percentuale di campo - Variabile che traccia la rappresentazione del valore digitale rispetto al campo definito dal valore di campo inferiore e dal valore di campo superiore, per le modalità operative normali. Le unità di questa variabile sono sempre in percentuale. | R | Float | 34 |
Name | ID | Label | Description | Type | Access | Class |