Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
device_flags | 00A0 | Dev flags | Field Device Flags- Describes special features of the Field Device that affect the Data Link Layer | R | BitEnum | 2048 |
analog_channel_saturated1 | 103D | AO saturated | Field Device Specific Dynamic Variable Analog Output Saturated- Data that indicates which of the Analog Outputs are, or are not, saturated. The analog and digital Analog Outputs for the Dynamic Variable are beyond their limits and no longer represent the true applied process. | R | BitEnum | 2051 |
analog_channel_fixed1 | 1040 | AO fixed | Field Device Specific Dynamic Variable Analog Output Fixed- Data that indicates which of the Analog Outputs are, or are not, Fixed. The analog and digital Analog Outputs for the Dynamic Variable are held at a constant value (depending on the Mode of the Field Device). They will not respond to the applied process. | R | BitEnum | 2051 |
analog_channel_saturated_codes | 08D6 | R/W | Enum | 4096 | ||
analog_channel_fixed_codes | 08D7 | R/W | Enum | 4096 | ||
burst_mode_select | 0FFF | Burst mode | Burst Mode Select- Selects the mode for the Burst Mode functionality. If Burst is enabled the Field Device will generate HART messages on the Link without individual requests from the Host. | R/W | Enum | 128 |
loopCurrent | 00ED | Loop current | Corriente de lazo: Valor de la corriente de lazo tal como lo percibe el dispositivo. | R | Float | 66 |
loop_alarm_code | 00EC | AO Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 64 |
loop_flags | 00E7 | Channel flags | Analog Channel Flags- Defines the characteristics of the Analog Channel | R | BitEnum | 64 |
percentRange | 00E9 | PV % rnge | Porcentaje de rango: Variable que rastrea la representación del valor digital con respecto al rango definido por el valor de rango inferior y el valor de rango superior, para modos de funcionamiento normales. Las unidades de esta variable siempre son en porcentaje. | R | Float | 34 |
Name | ID | Label | Description | Type | Access | Class |