Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
fDefaultSupplyPressure | 40BE | Supply Pressure | Supply Pressure | R/W | Float | 8 |
nTuneAggressiveness | 40BF | Agressiveness | Agressiveness | R/W | Integer | 8 |
cTuneFlags | 40C0 | cTuneFlags | The selections for autotune algorithm. | R/W | Enum | 8 |
cTuneCompletionCode | 40F1 | cTuneCompletionCode | cTuneCompletionCode(TBD) | R | Unsigned | 8 |
cAirAction | 4019 | Air Action | Air Action- configures the actuator to operate as Air to Close, or Air to Open. | R | Enum | 8 |
nSlotNumber | 4043 | Slot | Select the slot number(0-7), and load the specific tune data. Note: When the selector on the device indicates to 8 to F, means the device is configurated to ATC and the number of slots for ATC is still from 0 to 7. | R/W | Enum | 4096 |
nP | 404E | P | Proportional gain in %. Common values are 50 for small valves up to 4000 for large valves. Must be between 0 and 5000. | R/W | Unsigned | 8 |
nI | 404F | I | Integral time or reset time in 1/10 s. Higher values of I cause less integral action, however a value of 0 gives no integral action. Common values are 10 to 200. Values between 0 and 1000. | R/W | Unsigned | 8 |
nD | 4050 | D | Derivative time or rate time in milliSeconds. Common values are 10 to 100. Values between 0 and 200. | R/W | Unsigned | 8 |
nPadj | 4051 | Padj | Coefficient added to P when the valve is exhausting and compensates the variation in filling and exhausting speed. Can be positive or negative value range between -3000 to +3000. | R/W | Integer | 8 |
Name | ID | Label | Description | Type | Access | Class |