Name ID Label Description Type Access Class
fDefaultSupplyPressure 40BE Supply Pressure Supply Pressure R/W Float 8
nTuneAggressiveness 40BF Agressiveness Agressiveness R/W Integer 8
cTuneFlags 40C0 cTuneFlags The selections for autotune algorithm. R/W Enum 8
cTuneCompletionCode 40F1 cTuneCompletionCode cTuneCompletionCode(TBD) R Unsigned 8
cAirAction 4019 Air Action Air Action- configures the actuator to operate as Air to Close, or Air to Open. R Enum 8
nSlotNumber 4043 Slot Select the slot number(0-7), and load the specific tune data. Note: When the selector on the device indicates to 8 to F, means the device is configurated to ATC and the number of slots for ATC is still from 0 to 7. R/W Enum 4096
nP 404E P Proportional gain in %. Common values are 50 for small valves up to 4000 for large valves. Must be between 0 and 5000. R/W Unsigned 8
nI 404F I Integral time or reset time in 1/10 s. Higher values of I cause less integral action, however a value of 0 gives no integral action. Common values are 10 to 200. Values between 0 and 1000. R/W Unsigned 8
nD 4050 D Derivative time or rate time in milliSeconds. Common values are 10 to 100. Values between 0 and 200. R/W Unsigned 8
nPadj 4051 Padj Coefficient added to P when the valve is exhausting and compensates the variation in filling and exhausting speed. Can be positive or negative value range between -3000 to +3000. R/W Integer 8