名称 ID 标签 描述 类型 访问 分类
fPosErrorTime 402D Pos Error Time Position Error Time- time before to set the warning when position error exceeds the configured position error limit. This time must be between 1 s and 328 s. 读/写 浮点 8
cPosFailEnable 41D4 Position Fail Enable Position Fail- enable position fail testing. 读/写 枚举 8
fPosFailTime 41D3 Pos Fail Time Position Fail Time- Time before to put the valve in failsafe mode. This time must be >= 20 s and below 328 s and in any case 2s greater than Time 1 However to inhibit failsave mode set -1 s. 读/写 浮点 8
fNearPos 402E Near Closed Value Near Closed Position- Value of valve position below which the user considers the valve as being near closed position. Used in continuous diagnostic calculations. Must be between 0 and 20%. 读/写 浮点 8
cStopLowHighFlag 41DD Stop Adjust Flag 枚举 8
fLowSignal 4002 Low Signal Low Input Signal- Lower range value of input signal for valve closed (direct acting) or lower range value of input signal for valve open (reverse acting). Must be between 3.8 mA and 14 mA. 读/写 浮点 8
fHighSignal 4003 High Signal High Input Signal- high input signal for valve open (direct acting) or high input signal for valve close (reverse acting). Must be between 8 mA et 20.2 mA. The difference between Lower Range Value and Upper Range Value (span) must be at least 5 mA. 读/写 浮点 8
cCurve 41E9 Select Storage Selects which curve the recently created valve signature is stored to. 读/写 枚举 8
bCalibrationSensor 41DF Calibration Sensor Calibration Sensor. 读/写 枚举 4096
bCalibrationType 41E0 Calibration Type Calibration Type. 读/写 枚举 4096
名称 ID 标签 描述 类型 访问 分类