Name ID Label Description Type Access Class
cBumplessSpeed 4037 Transfer Time Transfer Time is approximately the numberof seconds required to move the valve 100%toward the signal position. It is between 0 and 255 sec/100%. R/W Unsigned 8
cStrokingSpeed 4212 Stroking Limit Stroking Limit R/W Unsigned 8
cPresUnits 4010 Pressure Unit Pressure Unit- The actual pressure reported by the SVI3 can be in psi, bar or kPa. R/W Enum 8
cLanguage 4004 LCD Language Language Displayed- Choice of languages displayed on the SVI3 LCD. R/W Enum 8
fOpenStopAdj 41C3 Open Stop Adj Open Stop Adjustment- This value must be between 60%-100%.For some valves the open position stop exceeds the nominal travel of the valve.By entering a value, the position calibration can be adjusted to nominal travel. R/W Float 8
fCloseStopAdj 4215 Close Stop Adj Close Stop Adjustment- NOT IMPLEMENTED YET. R/W Float 8
nP 4022 P Proportional gain in %. Common values are 50 for small valves up to 4000 for large valves. Must be between 1 and 5000. R/W Unsigned 10
nI 4023 I Integral time or reset time in 1/10 s. Higher values of I cause less integral action, however a value of 0 gives no integral action. Common values are 10 to 200. Values between 0 and 1000. R/W Unsigned 10
nD 4024 D Derivative time or rate time in milliSeconds. Common values are 10 to 100. Values between 0 and 200. R/W Unsigned 10
nPadj 4025 Padj Coefficient added to P when the valve is exhausting and compensates the variation in filling and exhausting speed. Can be positive or negative value range between -3000 to +3000. R/W Integer 10