Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
fP2 | 4044 | fP2 | W | Float | 8 | |
nIPOutput | 4084 | I/P Output | Set constant current on the I/P to adjust the pneumatic block. | W | Unsigned | 8 |
nTotalTravel | 406E | total travel | Total number of valve strokes. | R | Integer | 16 |
nTimeClosed | 406F | time closed | Time in hours for valve closed. | R | Integer | 16 |
nTimeOpen | 4070 | time open | Time in hours for valve open. | R | Integer | 16 |
nTimeNear | 4071 | time near closed | Time in hours for valve near closed. | R | Integer | 16 |
nCycles | 4072 | nbr cycles | Number of cycles (direction changes). | R | Integer | 16 |
cSpeed | 40A3 | Speed | Valve speed motion for record data. Mini is 1 and maxi is 10. | R/W | Integer | 8 |
nResponseO | 4073 | strok. time open | Fastest time to open the valve on the full stroke .This value is given from the standard diagnostic calculations. | R | Integer | 16 |
nResponseC | 4074 | strok. time close | Fastest time to close the valve on the full stroke. This value is given from the standard diagnostic calculations. | R | Integer | 16 |
Name | ID | Label | Description | Type | Access | Class |