Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
analog_alarm_code | 4000 | AO Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 64 |
fPos | 4001 | valve pos | Indicate the actual valve position in % with closed 0 % and opened 100 % | R | Float | 10 |
cPosUnits | 4002 | position unit | Unit for valve position | R | Enum | 8 |
fPres | 4003 | act pres | Indicate the actual valve pressure in its engineering unit. | R | Float | 10 |
cPresUnits | 4005 | pressure unit | The act. pressure reported by the SVI II can be in psi, bar or kPa | R/W | Enum | 8 |
fSignal | 4006 | inp sig | Input signal and current loop in mA | R | Float | 10 |
cSignalUnits | 4008 | Signal unit | Unit for Input Signal | R | Enum | 8 |
input_percent_range | 4009 | inp sig | Input signal and current loop in percent | R | Float | 10 |
sensor_serial_number | 400A | PV Snsr s/n | Número de serie del sensor: Identifica de manera única el sensor del que se deriva principalmente la representación del valor digital o la variable del dispositivo de campo. | R/W | Unsigned | 2048 |
fManualPos | 4039 | man pos | Manual valve setpoint in %. Value mut be between -5.0% and +105.0% . | R/W | Float | 10 |