Name ID Label Description Type Access Class
fPosErrorTime 4079 Pos Error Time Position Error Time- time before to set the warning when position error exceeds the configured position error limit. This time must be between 1 s and 328 s. R/W Float 8
cPosFailEnable 40C8 Position Fail Enable Position Fail- enable position fail testing R/W Enum 8
fPosFailTime 40C7 Pos Fail Time Position Fail Time- Time before to put the valve in failsafe mode. This time must be >= 20 s and below 328 s and in any case 2s greater than Time 1 However to inhibit failsave mode set -1 s. R/W Float 8
fNearPos 4076 Near Closed Value Near Closed Position- Value of valve position below which the user considers the valve as being near closed position. Used in continuous diagnostic calculations. Must be between 0 and 20%. R/W Float 8
cStopLowHighFlag 40CD Stop Adjust Flag W BitEnum 8
fLowSignal 402E Low Signal Low Input Signal- Lower range value of input signal for valve closed (direct acting) or lower range value of input signal for valve open (reverse acting). Must be between 3.8 mA and 14 mA. R/W Float 8
fHighSignal 402F High Signal High Input Signal- high input signal for valve open (direct acting) or high input signal for valve open (reverse acting). Must be between 8 mA et 20.2 mA. The difference between Lower Range Value and Upper Range Value (span) must be at least 5 mA. R/W Float 8
cCurve 40D8 Select Storage Selects which curve the recently created valve signature is stored to R/W Enum 8
bCalibrationSensor 40CE Calibration Sensor Calibration Sensor R/W BitEnum 4096
bCalibrationType 40CF Calibration Type Calibration Type R/W BitEnum 4096