Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
cBumplessSpeed | 408C | Transfer Time | Transfer Time is approximately the numberof seconds required to move the valve 100%toward the signal position. It is between 1 and 255 sec/100%. | R/W | Unsigned | 8 |
cStrokingSpeed | 40EB | Stroking Limit | ???? | R/W | Unsigned | 8 |
cPresUnits | 405E | Pressure Unit | Pressure Unit- The actual pressure reported by the SVI II AP can be in psi, bar or kPa | R/W | Enum | 8 |
cLanguage | 4083 | LCD Language | Language Displayed- Choice of languages displayed on the SVI II AP LCD. | R/W | Enum | 8 |
fOpenStopAdj | 40C9 | Open Stop Adj | Open Stop Adjustment- This value must be between 60%-100%.For some valves the open position stop exceeds the nominal travel of the valve.By entering a value, the position calibration can be adjusted to nominal travel. | R/W | Float | 8 |
fCloseStopAdj | 40EE | Close Stop Adj | Close Stop Adjustment- NOT IMPLEMENTED YET | R/W | Float | 8 |
nP | 406C | P | Proportional gain in %. Common values are 50 for small valves up to 4000 for large valves. Must be between 0 and 5000. | R/W | Unsigned | 10 |
nI | 406D | I | Integral time or reset time in 1/10 s. Higher values of I cause less integral action, however a value of 0 gives no integral action. Common values are 10 to 200. Values between 0 and 1000. | R/W | Unsigned | 10 |
nD | 406E | D | Derivative time or rate time in milliSeconds. Common values are 10 to 100. Values between 0 and 200. | R/W | Unsigned | 10 |
nPadj | 406F | Padj | Coefficient added to P when the valve is exhausting and compensates the variation in filling and exhausting speed. Can be positive or negative value range between -3000 to +3000. | R/W | Integer | 10 |