Name ID Label Description Type Access Class
fPosBand 4071 Pos Error Band Position Error Band- Value corresponding to the maximun error (in % opening) between the setpoint and the valve position allowed, before setting a status flag regards the selection of associated variable Time. Value must be between 0.5% and 100.0% . R/W Float 8
cPosErrorEnable 4070 Pos Error Enable Enable Position Error- enable position error testing R/W Enum 8
fPosErrorTime 4072 Pos Error Time Position Error Time- time before to set the warning when position error exceeds the configured position error limit. This time must be between 1 s and 328 s. R/W Float 8
cPosFailEnable 40F4 Position Fail Enable Position Fail- enable position fail testing R/W Enum 8
fPosFailTime 40F3 Pos Fail Time Position Fail Time- Time before to put the valve in failsafe mode. This time must be >= 20 s and below 328 s and in any case 2s greater than Time 1 However to inhibit failsave mode set -1 s. R/W Float 8
fNearPos 406F Near Closed Value Near Closed Position- Value of valve position below which the user considers the valve as being near closed position. Used in continuous diagnostic calculations. Must be between 0 and 20%. R/W Float 8
cStopLowHighFlag 40FB Stop Adjust Flag W BitEnum 8
fLowSignal 4021 Low Signal Low Input Signal- Lower range value of input signal for valve closed (direct acting) or lower range value of input signal for valve open (reverse acting). Must be between 3.8 mA and 14 mA. R/W Float 8
fHighSignal 4022 High Signal High Input Signal- high input signal for valve open (direct acting) or high input signal for valve close (reverse acting). Must be between 8 mA et 20.2 mA. The difference between Lower Range Value and Upper Range Value (span) must be at least 5 mA. R/W Float 8
cCurve 4107 Select Storage Selects which curve the recently created valve signature is stored to R/W Enum 8