Name ID Label Description Type Access Class
bConfigFlags0_Air 4020 Air Action Air Action- configures the actuator to operate as Air to Close, or Air to Open. R/W Enum 8
bConfigFlags0_Bumpless 4086 Bumpless Transfer Bumpless Transfer- enables or disables the bumpless transfer mode. R/W Enum 8
bConfigFlags1_ProtectLimits 4088 Allow Override Limit Allow diag. and self-tune to override limits R/W Enum 8
bConfigFlags1_LowerLimit 408B Pos Limit Low To enable or disable position lower limit R/W Enum 8
bConfigFlags1_UpperLimit 408D Pos Limit High To enable or disable position upper limit R/W Enum 8
bConfigFlags1_TightShutoff 408F Tight Shutoff Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Set the TS value between -1% and 20%, then enable the TS function. R/W Enum 8
bConfigFlags1_Characterization 4085 Characterization Cam Configuration Flags- cam used - defines relationship between flow capacity (Cv) and percentage opening of the valve. Several cams are available: linear; =%50; =%30; quick opening coefficient of 50; custom; CamFlex=%. R/W Enum 8
bConfigFlags2 407F Local Buttons Button Configuration Flags- Defines lock level for SVI II AP buttons to avoid unintended modifications. R/W Enum 8
bConfigFlags3 40F2 Setpoint Mode Setup Configuration Flags- These options determine whether the controller setpoint will be in local, local only, remote or last mode on startup. R/W Enum 8
fTSLimit 4090 Tight Shutoff Value Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Value between -1% and 20% and not to include. R/W Float 8
Name ID Label Description Type Access Class