Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
bConfigFlags0_Air | 4020 | Air Action | Air Action- configures the actuator to operate as Air to Close, or Air to Open. | R/W | Enum | 8 |
bConfigFlags0_Bumpless | 4086 | Bumpless Transfer | Bumpless Transfer- enables or disables the bumpless transfer mode. | R/W | Enum | 8 |
bConfigFlags1_ProtectLimits | 4088 | Allow Override Limit | Allow diag. and self-tune to override limits | R/W | Enum | 8 |
bConfigFlags1_LowerLimit | 408B | Pos Limit Low | To enable or disable position lower limit | R/W | Enum | 8 |
bConfigFlags1_UpperLimit | 408D | Pos Limit High | To enable or disable position upper limit | R/W | Enum | 8 |
bConfigFlags1_TightShutoff | 408F | Tight Shutoff | Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Set the TS value between -1% and 20%, then enable the TS function. | R/W | Enum | 8 |
bConfigFlags1_Characterization | 4085 | Characterization | Cam Configuration Flags- cam used - defines relationship between flow capacity (Cv) and percentage opening of the valve. Several cams are available: linear; =%50; =%30; quick opening coefficient of 50; custom; CamFlex=%. | R/W | Enum | 8 |
bConfigFlags2 | 407F | Local Buttons | Button Configuration Flags- Defines lock level for SVI II AP buttons to avoid unintended modifications. | R/W | Enum | 8 |
bConfigFlags3 | 40F2 | Setpoint Mode | Setup Configuration Flags- These options determine whether the controller setpoint will be in local, local only, remote or last mode on startup. | R/W | Enum | 8 |
fTSLimit | 4090 | Tight Shutoff Value | Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Value between -1% and 20% and not to include. | R/W | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |