Loading…
名称 ID 标签 描述 类型 访问 分类
nD 4067 D Derivative time or rate time in milliSeconds. Common values are 10 to 100. Values between 0 and 200. 读/写 无符号 10
nPadj 4068 Padj Coefficient added to P when the valve is exhausting and compensates the variation in filling and exhausting speed. Can be positive or negative value range between -3000 to +3000. 读/写 整型 10
nBeta 4069 Beta Nonlinear gain factor. When beta is 0, the proportional gain is linear, otherwise the gain P is a function of error. The larger the beta, the smaller the gain for small error. Typical beta value is 7 or 8. Beta is ranging from -9 to +9. 读/写 整型 10
nDamping 40F5 Damping Coefficient to increase the valve response for some applications. A value of 0 gives no Damping. 0 to 250 seconds is for slow down in both directions. -1 to -250 is for slow down in OPEN direction ONLY. -1001 to -1250 is for slow down in CLOSE direction ONLY. 读/写 整型 10
nPosComp 406B Position Comp. The response of the valve is different when the valve is nearly closed than when nearly open. This coefficient allows the user to make adjustments to try to equalize the valve response. Normal value is 6 and this value is ranging from 2 to 20. 读/写 无符号 10
nDeadZone 406A Dead Zone When the valve position is within the setpoint +/- the dead zone and, no additional position control is performed. This value is normally 0%. Used to avoid limit cycling for high friction valves. Range is 0 to 5%. 读/写 无符号 10
nDeadBand 406C Boost Boost- Compensates for the pnuematic dead band. Value ranges between 0 and 20. 读/写 无符号 10
nNonLinear 4125 Non Linear Non Linear 无符号 10
nReserved1 4126 Reserved 1 Reserved 1 无符号 10
nReason 40F1 Auto Tune Fault Reason for Auto Tune failure 无符号 10
名称 ID 标签 描述 类型 访问 分类