名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
fLowerPosLimits | 408C | Limit Low | Lower Position Limit- The SVI II AP allows the user to establish software limit stops. The control functions will NOT allow the valve position to be lower than the lower position limit. However this option DOES NOT PROVIDE MECHANICAL STOPS for the valve. During an electrical or an air failure the valve will go to the failsafe position without regard to the software limit stops. The manual position full closed or full open will similarly ignore limit stops. The value should be set between -10 and 50.0 not to include | 读/写 | 浮点 | 8 |
fUpperPosLimits | 408E | Limit High | Upper Position Limit- The SVI II AP allows the user to establish software limit stops. The control functions will NOT allow the valve position to be above than the upper position limit.However this option DOES NOT PROVIDE MECHANICAL STOPS for the valve. During an electrical or an air failure the valve will go to the failsafe position without regard to the software limit stops. The manual position full closed or full open will similarly ignore limit stops. | 读/写 | 浮点 | 8 |
cBumplessSpeed | 4087 | Transfer Time | Transfer Time is approximately the numberof seconds required to move the valve 100%toward the signal position. It is between 1 and 255 sec/100%. | 读/写 | 无符号 | 8 |
cStrokingSpeed | 411F | Stroking Limit | Stroking Limit | 读/写 | 无符号 | 8 |
cPresUnits | 4058 | Pressure Unit | Pressure Unit- The actual pressure reported by the SVI II AP can be in psi, bar or kPa | 读/写 | 枚举 | 8 |
cLanguage | 407E | LCD Language | Language Displayed- Choice of languages displayed on the SVI II AP LCD. | 读/写 | 枚举 | 8 |
fOpenStopAdj | 40EA | Open Stop Adj | Open Stop Adjustment- This value must be between 60%-100%.For some valves the open position stop exceeds the nominal travel of the valve.By entering a value, the position calibration can be adjusted to nominal travel. | 读/写 | 浮点 | 8 |
fCloseStopAdj | 4122 | Close Stop Adj | Close Stop Adjustment- NOT IMPLEMENTED YET | 读/写 | 浮点 | 8 |
nP | 4065 | P | Proportional gain in %. Common values are 50 for small valves up to 4000 for large valves. Must be between 0 and 5000. | 读/写 | 无符号 | 10 |
nI | 4066 | I | Integral time or reset time in 1/10 s. Higher values of I cause less integral action, however a value of 0 gives no integral action. Common values are 10 to 200. Values between 0 and 1000. | 读/写 | 无符号 | 10 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |