Name ID Label Description Type Access Class
fLLevelAlarm 4022 Low alarm level Alarm threshold in the same engineering units as the level of liquid corresponding to the level value under which the transmitter set a low alarm or to go to failsafe mode regarding Time1 and Time 2 R/W Float 8
fULevelAlarm 4023 High alarm level Alarm threshold in the same engineering units as level of liquid corresponding to the level value above which the transmitter set a high alarm or to go to failsafe mode regarding Time1 and Time 2 R/W Float 8
nPosTime1 407C time 1 Time before to set an alarm : this time must be >= -1 s and below 1000 s R/W Integer 8
nPosTime2 407D time 2 Time before to go to failsafe mode : this time must be >= -1 s and below 1000 s. R/W Integer 8
fLSignal 4044 low signal Low output current for low level (direct acting) or low output current for high level (reverse acting). Must be between 3.8 mA and 14 mA. R/W Float 64
fUSignal 4045 high signal High output current for high level (direct acting) or high output current for low level (reverse acting). Must be between 8 mA et 20.5 mA. R/W Float 64
fZeroShift 4046 zero shift Value in percentage of calibration scale (zero/span) to shift the ZERO in an other position . The current output is automatically re-ajusted at this new ZERO position. R/W Float 8
fReduceSpan 4047 reduce span Value in percentage of calibration scale (zero/span) to reduce the SPAN .The current output is automatically re-ajusted to take into account this new SPAN. R/W Float 8
fTempHallCal 404F hall temp cal Temperature in Celcius for the electronic head during the ZERO and SPAN calibration . R/W Float 8
fTempTubeCal 40A6 tube temp cal Temperature in Celcius for the torque tube during the ZERO and SPAN calibration . R/W Float 8