名称 ID 标签 描述 类型 访问 分类
fLLevelAlarm 4022 Low alarm level Alarm threshold in the same engineering units as the level of liquid corresponding to the level value under which the transmitter set a low alarm or to go to failsafe mode regarding Time1 and Time 2 读/写 浮点 8
fULevelAlarm 4023 High alarm level Alarm threshold in the same engineering units as level of liquid corresponding to the level value above which the transmitter set a high alarm or to go to failsafe mode regarding Time1 and Time 2 读/写 浮点 8
nPosTime1 407C time 1 Time before to set an alarm : this time must be >= -1 s and below 1000 s 读/写 整型 8
nPosTime2 407D time 2 Time before to go to failsafe mode : this time must be >= -1 s and below 1000 s. 读/写 整型 8
fLSignal 4044 low signal Low output current for low level (direct acting) or low output current for high level (reverse acting). Must be between 3.8 mA and 14 mA. 读/写 浮点 64
fUSignal 4045 high signal High output current for high level (direct acting) or high output current for low level (reverse acting). Must be between 8 mA et 20.5 mA. 读/写 浮点 64
fZeroShift 4046 zero shift Value in percentage of calibration scale (zero/span) to shift the ZERO in an other position . The current output is automatically re-ajusted at this new ZERO position. 读/写 浮点 8
fReduceSpan 4047 reduce span Value in percentage of calibration scale (zero/span) to reduce the SPAN .The current output is automatically re-ajusted to take into account this new SPAN. 读/写 浮点 8
fTempHallCal 404F hall temp cal Temperature in Celcius for the electronic head during the ZERO and SPAN calibration . 读/写 浮点 8
fTempTubeCal 40A6 tube temp cal Temperature in Celcius for the torque tube during the ZERO and SPAN calibration . 读/写 浮点 8