Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
remote_seal_fill_fluid | 400D | リモート封入液 | Remote Seal Fill Fluid- Fluid material in the device remote seal. | R/W | Enum | 2048 |
module_range_code | 4000 | モジュール レンジ | Module range- pressure range located on the side of the sensor | R | Enum | 2048 |
temperature_value | 4001 | Amp temp | Field Device Variable Value- Digital value that changes with respect to process or ambient temperature over time with no user intervention. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. | R | Float | 10 |
temperature_units | 4018 | Amp temp unit | Field Device Variable Unit- Digital unit that the variable will be displayed with. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. | R | Enum | 8 |
upper_display_value | 401C | UDV | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. UDV: Upper Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 | R/W | Float | 256 |
lower_display_value | 401D | LDV | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. LDV: Lower Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 | R/W | Float | 256 |
digit_number_under_decimal_point | 401E | Digit_DP | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. Digit_DP: Digit under Decimal Point- Available range is from 0 to 4 as below; 0 (XXXXX) 1 (XXXX.X) 2 (XXX.XX) 3 (XX.XXX) 4 (X.XXXX) | R/W | Unsigned | 256 |
unit_code | 401F | LCD_Unit | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. There are 4 groups as below. All units appear in series. 1)Pressure(DISP=LIN)2)Level(DISP=LIN) 3)Flow(DISP=SQR) 4)Special(%and None) | R/W | Enum | 256 |
option | 4020 | LCD_Opt. | XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. | R/W | Unsigned | 256 |
Cut_Point_value | 4005 | Cut_Pt % | Cut_Pt: Low Cut Point- Dimension in % Flow at Calibrated Range, affects Analog Output and Transmitter LCD in SQR mode only. Available range is from 0% to 20% Flow. | R/W | Float | 16 |
Cut_Mode_value | 4006 | Cut_Mode | Cut_Mode: Low Cut Mode- Output mode below Low Cut Point, affects Analog Output and Transmitter LCD in SQR mode only. Available mode is LINEAR or ZERO. | R/W | Enum | 16 |
burnout_current_overscale | 4027 | Overscale | Overscale_Current is able to set in the range from 20.8mA to 21.6mA. | R/W | Enum | 16 |
burnout_current_underscale | 4028 | Underscale | Underscale_Current is able to set in the range from 3.2mA to 3.8mA. | R/W | Enum | 16 |
burnout_current_underscale_exp | 4035 | Underscale | Underscale_Current is able to set in the range from 3.2mA to 4.0mA. | R/W | Enum | 16 |
burnout_current_overscale_exp | 4036 | Overscale | Overscale_Current is able to set in the range from 20.0mA to 22.5mA. | R/W | Enum | 16 |
saturation_current_lower | 4037 | Saturate Lo | Saturated Low Current is able to set in the range from 3.2mA to 4.0mA. | R/W | Enum | 16 |
saturation_current_upper | 4038 | Saturate Hi | Saturated High Current is able to set in the range from 20.0mA to 22.5mA. | R/W | Enum | 16 |
select_spec | 4039 | Select Spec | Select Spec- Select specification of Burnout/Saturation. | R/W | Enum | 16 |
Amp_Temp_Min | 4040 | Amp Min | Amp Min- Min temperature of the amp. | R | Float | 16 |
Amp_Temp_Max | 4041 | Amp Max | Amp Max- Max temperature of the amp. | R | Float | 16 |
Cell_Temp_Min | 4042 | Cell Min | Cell Min- Min temperature of the cell. | R | Float | 16 |
Cell_Temp_Max | 4043 | Cell Max | Cell Max- Max temperature of the cell. | R | Float | 16 |
min_and_max_temperature_mode | 4044 | Action Mode | Stop: Stop recording of temp data. Restart: Restart recording of temp data. Clear: Clear min/max temp data. | W | Enum | 16 |
change_write_protect | 4049 | Protect | At First, Input password. and Set Enable/Disable of Write Protect. | R/W | Enum | 16 |
access_password_value | 404A | Password | Password- Current password for setting Enable/Disable of Write Protect. | W | PackedAscii | 256 |
Name | ID | Label | Description | Type | Access | Class |