Name ID Label Description Type Access Class
remote_seal_fill_fluid 400D リモート封入液 Remote Seal Fill Fluid- Fluid material in the device remote seal. R/W Enum 2048
module_range_code 4000 モジュール レンジ Module range- pressure range located on the side of the sensor R Enum 2048
temperature_value 4001 Amp temp Field Device Variable Value- Digital value that changes with respect to process or ambient temperature over time with no user intervention. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. R Float 10
temperature_units 4018 Amp temp unit Field Device Variable Unit- Digital unit that the variable will be displayed with. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. R Enum 8
upper_display_value 401C UDV XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. UDV: Upper Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 R/W Float 256
lower_display_value 401D LDV XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. LDV: Lower Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 R/W Float 256
digit_number_under_decimal_point 401E Digit_DP XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. Digit_DP: Digit under Decimal Point- Available range is from 0 to 4 as below; 0 (XXXXX) 1 (XXXX.X) 2 (XXX.XX) 3 (XX.XXX) 4 (X.XXXX) R/W Unsigned 256
unit_code 401F LCD_Unit XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. There are 4 groups as below. All units appear in series. 1)Pressure(DISP=LIN)2)Level(DISP=LIN) 3)Flow(DISP=SQR) 4)Special(%and None) R/W Enum 256
option 4020 LCD_Opt. XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. LCD_Opt.: AZ_LCD_Option is not used now. R/W Unsigned 256
Cut_Point_value 4005 Cut_Pt % Cut_Pt: Low Cut Point- Dimension in % Flow at Calibrated Range, affects Analog Output and Transmitter LCD in SQR mode only. Available range is from 0% to 20% Flow. R/W Float 16
Cut_Mode_value 4006 Cut_Mode Cut_Mode: Low Cut Mode- Output mode below Low Cut Point, affects Analog Output and Transmitter LCD in SQR mode only. Available mode is LINEAR or ZERO. R/W Enum 16
burnout_current_overscale 4027 Overscale Overscale_Current is able to set in the range from 20.8mA to 21.6mA. R/W Enum 16
burnout_current_underscale 4028 Underscale Underscale_Current is able to set in the range from 3.2mA to 3.8mA. R/W Enum 16
cell_body_no 400C Cell B/N Cell B/N: Cell_Body_No- Manufacturer Cell Body Number consist of 8 digits(max.), read only. R PackedAscii 2048
model_code 4014 Model_Code Model Code- Manufacturer Model Code consist of 16 digits(max.) not including hyphen. R/W PackedAscii 2048
serial_number 4015 Ser-No Ser-No: Serial_Number- Manufacturer Serial Number consist of 8 digits(max.), read only. R PackedAscii 2048
unique_device_type_code 07ED R/W Enum 128
rosemount_model_code 07F5 R/W Enum 2048
rosemount_analytical_model_code 07F6 R/W Enum 2048
kayray_model_code 07F7 R/W Enum 2048
micro_motion_model_code 07F8 R/W Enum 2048
units_code 07E9 R/W Enum 4096
transfer_function_code 07EA R/W Enum 4096
material_code 07EC R/W Enum 4096
alarm_selection_code 07EB R/W Enum 4096
write_protect_code 07EE R/W Enum 2048
company_identification_code 07EF R/W Enum 128
burst_mode_control_code 07F0 R/W Enum 128
physical_signaling_codes 07F1 R/W Enum 2048
flag_assignment 07F2 R/W Enum 128
operating_mode_code 07F3 R/W Enum 2048
analog_output_numbers_code 07F4 R/W Enum 4096
response_code 0096 コマンド固有応答コード - フィールド機器応答で戻されるデータで, ホスト要求で送信されたコマンドの成功具合を示します。この情報はホスト要求データまたはコマンド自体によって変わる場合があります。 R/W Enum 129
comm_status 0098 通信エラー内容 - ホストの要求に対しフィールド機器が次のような状態のときエラーになります。コマンドを受取れないとき, ホストの要求に対しフィールド機器が変更できない場合。 R/W BitEnum 131
device_status 0097 フィールド機器ステータス - フィールド機器のハードウェア/バリアブルの状態/オペレーティング ステータス/内部処理に対して検出されたコンディションを表示します。 R/W BitEnum 131
manufacturer_id 0099 メーカー メーカー識別コード - 通常, 会社名を使用し, フィールド機器の製造上の責任者を明確にします。 R Enum 128
device_type 009A モデル モデル - フィールド機器のタイプを表し, メーカーごとに独自に決められたナンバーで, 通常, 機器の照会に使用されます。 R Enum 128
request_preambles 009B プリアンブル数 プリアンブル数 - ホストの要求に対しフィールド機器が対応できるプリアンブルの数です。 R Unsigned 128
universal_revision 009C ユニバーサル レビジョン ユニバーサル レビジョン - フィールド機器を適合させるユニバーサル機器ディスクリプションのレビジョンです。 R Unsigned 128
transmitter_revision 009D フィールド機器レビジョン フィールド機器レビジョン - フィールド機器を適合させるフィールド機器スペシフィック機器ディスクリプションのレビジョンです。 R Unsigned 128
software_revision 009E ソフトウェア レビジョン フィールド機器ソフトウェア レビジョン - これはソフトウェア又はファームウェアのレビジョンのことで, フィールド機器に書込まれています。 R Unsigned 2048
hardware_revision 009F ハードウェア レビジョン ハードウェア レビジョン - フィールド機器のエレクトロニクス ハードウェアのレビジョンです。 R Unsigned 2048
physical_signaling_code 00AB フィジカル シグナル コード フィジカル シグナル コード - フィジカル シグナル コードは, HART コミュニケーション ポートのハードウェアに対して与えられているフィジカル レイヤーのタイプを表示しています。 R Enum 2048
device_flags 00A0 機器しるし フィールド機器フラグ - データ リンク レイヤーに影響を及ぼす, フィールド機器の特殊な機能を示します。 R BitEnum 128
device_id 00A1 機器 ID 機器 ID - フィールド機器の識別にはメーカー名称及び機器タイプの組合せで行います。これはユーザーで変更することはできません。 R Unsigned 128
polling_address 00A2 ポール アドレス ポール アドレス - アドレスはホストによるフィールド機器の識別や, マルチドロップ モード及びアナログ出力固定モードのアナログ出力 1 のコントロールに使用されます。 W Unsigned 128
tag 00A3 タグ タグ - フィールド機器の設置に利用されるテキストのことです。このテキストはユーザーの自由に使うことができます。通常はフィールド機器に関連したプラントで唯一のラベルを使用します: プラント図面又はコントロール システムに使用されているラベル。また, この表示はデータ リンク レイヤーのアドレス管理にも使用しています。 R/W PackedAscii 2048
message 00A4 メッセージ メッセージ - フィールド機器に関するテキストを記録できます。このテキストは自由に使うことができます。これはスペックには影響しません。 R/W PackedAscii 2048
descriptor 00A5 記述 記述 - フィールド機器に関するテキストを記録できます。このテキストは自由に使うことができます。これはスペックには影響しません。 R/W PackedAscii 2048
date 00A6 日付 日付 - フィールド機器にグレゴリアン カレンダーの日付を記録できます。この日付は自由に使うことができます。これはスペックには影響しません。 R/W HartDate 2048