Name ID Label Description Type Access Class
remote_seal_fill_fluid 400D RS fill fluid Remote Seal Fill Fluid- Fluid material in the device remote seal. R/W Enum 2048
module_range_code 4000 Module rnge Module range- pressure range located on the side of the sensor R Enum 2048
temperature_value 4001 Amp temp Field Device Variable Value- Digital value that changes with respect to process or ambient temperature over time with no user intervention. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. R Float 10
temperature_units 4018 Amp temp unit Field Device Variable Unit- Digital unit that the variable will be displayed with. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. R Enum 8
upper_display_value 401C UDV XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. UDV: Upper Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 R/W Float 256
lower_display_value 401D LDV XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. LDV: Lower Disp Value- Available range is as below; -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to 99.999 -9.9999 to 9.9999 R/W Float 256
digit_number_under_decimal_point 401E Digit_DP XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. Digit_DP: Digit under Decimal Point- Available range is from 0 to 4 as below; 0 (XXXXX) 1 (XXXX.X) 2 (XXX.XX) 3 (XX.XXX) 4 (X.XXXX) R/W Unsigned 256
unit_code 401F LCD_Unit XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. There are 4 groups as below. All units appear in series. 1)Pressure(DISP=LIN)2)Level(DISP=LIN) 3)Flow(DISP=SQR) 4)Special(%and None) R/W Enum 256
option 4020 LCD_Opt. XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. LCD_Opt.: AZ_LCD_Option is not used now. R/W Unsigned 256
Cut_Point_value 4005 Cut_Pt % Cut_Pt: Low Cut Point- Dimension in % Flow at Calibrated Range, affects Analog Output and Transmitter LCD in SQR mode only. Available range is from 0% to 20% Flow. R/W Float 16
Cut_Mode_value 4006 Cut_Mode Cut_Mode: Low Cut Mode- Output mode below Low Cut Point, affects Analog Output and Transmitter LCD in SQR mode only. Available mode is LINEAR or ZERO. R/W Enum 16
burnout_current_overscale 4027 Overscale Overscale_Current is able to set in the range from 20.8mA to 21.6mA. R/W Enum 16
burnout_current_underscale 4028 Underscale Underscale_Current is able to set in the range from 3.2mA to 3.8mA. R/W Enum 16
cell_body_no 400C Cell B/N Cell B/N: Cell_Body_No- Manufacturer Cell Body Number consist of 8 digits(max.), read only. R PackedAscii 2048
model_code 4014 Model_Code Model Code- Manufacturer Model Code consist of 16 digits(max.) not including hyphen. R/W PackedAscii 2048
serial_number 4015 Ser-No Ser-No: Serial_Number- Manufacturer Serial Number consist of 8 digits(max.), read only. R PackedAscii 2048
unique_device_type_code 07ED R/W Enum 128
rosemount_model_code 07F5 R/W Enum 2048
rosemount_analytical_model_code 07F6 R/W Enum 2048
kayray_model_code 07F7 R/W Enum 2048
micro_motion_model_code 07F8 R/W Enum 2048
units_code 07E9 R/W Enum 4096
transfer_function_code 07EA R/W Enum 4096
material_code 07EC R/W Enum 4096
alarm_selection_code 07EB R/W Enum 4096
Name ID Label Description Type Access Class