Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
DS_Pos_Cmd | 409F | Control Command | The modified command signal, in percent of full stroke, which actually sets the controlled position of the valve. Control Command is generated after custom characterization, soft limits, and minimum position cutoff parameters are evaluated. 4-20 mA command and Control Command can differ if custom characterization, soft limits, or minimum position cutoff are active. | R | Integer | 66 |
DS_Pos_Deviation | 40A0 | Deviation | The difference between the modified position command (Control Command) signal and the stem position signal expressed in percent of full stroke. Deviation = Control Command - Position. | R | Integer | 34 |
DS_Pos_FB | 40A1 | Position | Actual stem position in percent of full stroke, as measured by the position stem position transducer. | R | Integer | 34 |
EC_Build_Day | 4049 | E. Code Build Day | R | Integer | 2048 | |
EC_Build_Hour | 404A | E. Code. Build Hour | R | Integer | 2048 | |
EC_Build_Min | 404B | E. Code Build Min. | R | Integer | 2048 | |
EC_Build_Month | 4048 | E. Code Build Mo. | R | Integer | 2048 | |
EC_Build_Sec | 404C | E. Code Build Sec. | R | Integer | 2048 | |
EC_Build_Year | 4047 | E. Code Build Yr. | R | Integer | 2048 | |
EC_Major | 40A2 | E. Code Major | Embedded code major version number. | R | Integer | 2048 |
Name | ID | Label | Description | Type | Access | Class |