Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
DC_Fail_Position | 4096 | Fail Position | Select the position to which the valve will fail (open or closed as determined by the spring position). | R/W | Enum | 32 |
DC_Model_BA | 4097 | Positioner Model | View whether the positioner has pressure sensors. 520 = No presure sensors, 521 = Has pressure sensors. | R/W | Enum | 2048 |
DC_Sing_Dbl_Acting | 4098 | Positioner Action | Select the positioner action (single or double acting). | R/W | Enum | 2048 |
DC_Valve_LR | 4099 | Motion | Select the type of valve the positioner is controlling (linear or rotary). | R/W | Enum | 2048 |
D_Gain | 409A | D-Gain | D-Gain anticipates overshoot based on the current velocity and dynamically adjusts movement so that overshoot does not occur. | R/W | Float | 32 |
DS_Cmd_Analog | 409B | 4-20 Command | Input 4-20mA command expressed in percent of full scale input. | R | Integer | 66 |
DS_Cmd_Digital | 409C | Digital Command | Enter the digital command value, in percent of full stroke. This variable is available only when the valve is being positioned by a digital command (digital source) rather than the 4-20mA analog signal (analog source). | R/W | Integer | 36 |
DS_Cmd_Source | 4045 | Command Source | Displays the source of the command signal (analog or digital). | R/W | Enum | 64 |
DS_Cmd_Source2 | 409D | Unused | R | Integer | 2048 | |
DS_MPC_flag | 409E | Position Cutoff | Displays state of Position Cut-off as defined in the Soft Limit / Characterization Menu. | R | Enum | 2 |
Name | ID | Label | Description | Type | Access | Class |