Name ID Label Description Type Access Class
ST1_SensorUpperLimit_1 4034 Sensor upper limit Indication of the upper, physical sensor range. R/W Float 2048
ST1_SensorLowerLimit_1 4035 Sensor lower limit Indication of the lower, physical sensor range. R/W Float 2048
ST1_SensorMaxIndicator_1 4063 Sensor max value Indication of the maximum measured temperature in the past. R Float 2
ST1_SensorMinIndicator_1 4064 Sensor min value Indication of the minimum measured temperature in the past. R Float 2
ST1_SensorOffset_1 4065 Sensor offset Setting of the zero adjustment of the measured sensor value. R/W Float 2048
ST1_SensorConnection_1 4036 Connection type Selection of the sensor connection type R/W Enum 2048
ST1_WireCompensation_1 4066 2-wire compensation Setting of the resistance for the 2-wire RTD compensation. R/W Float 2048
ST1_RjType_1 4037 Reference junction Selection of reference junction measurement for temperature compensation in thermocouples. R/W Enum 2048
ST1_FixedRjValue_1 4067 RJ preset value Setting of the value for the external temperature compensation. R/W Float 2048
ST1_CalVandusenA_1 4068 Call./v. Dusen coeff. A Setting of the Callendar/van Dusen coefficient A for the linearization based on the Callendar-Van Dusen method. R/W Float 2048