Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
Out_Value_4_20 | 401A | AO | Analog Output Value - Value that tracks the Digital Value representation, und normal operating modes. | R | Float | 66 |
Out_Value_Percent | 401B | PV value in % | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
Out_Range_Low | 400D | PV lo range value | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 34 |
Out_Range_High | 400C | PV up range value | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 34 |
Out_Mode | 402D | Analog output | Selection of standard operation 4..20 mA (small output signal by small process variables) or inverse operation 20..4 mA (small output signal on higher process variables). | R/W | Enum | 2048 |
Out_Damping | 402E | Filter time | Input for filter, from measurement recording to output. (0 to 60 seconds) | R/W | Float | 2048 |
Error_Mode | 400E | Fault condition | Select the fault information on sensor fault. When a sensor defect is recognised the transmitter transmits the defined output value. | R/W | Enum | 0 |
Loop_Test | 404A | Simulation mode | Simulation mode is used to change the device's operating mode. OFF for normal measure operation. ON for analog output simulation. The value of analog output can be inserted in the page Simulation value. | R/W | Enum | 0 |
Loop_Test_Value | 404B | Simulation value | Current at the output when simulation is set to ON. (value between 3.58 and 21.7 mA) | R/W | Float | 0 |
variable_array_index | 404D | R/W | Index | 4096 | ||
Name | ID | Label | Description | Type | Access | Class |