Name ID Label Description Type Access Class
Out_Value_4_20 401A AO Analog Output Value - Value that tracks the Digital Value representation, und normal operating modes. R Float 66
Out_Value_Percent 401B PV value in % Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
Out_Range_Low 400D PV lo range value Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 34
Out_Range_High 400C PV up range value Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 34
Out_Mode 402D Analog output Selection of standard operation 4..20 mA (small output signal by small process variables) or inverse operation 20..4 mA (small output signal on higher process variables). R/W Enum 2048
Out_Damping 402E Filter time Input for filter, from measurement recording to output. (0 to 60 seconds) R/W Float 2048
Error_Mode 400E Fault condition Select the fault information on sensor fault. When a sensor defect is recognised the transmitter transmits the defined output value. R/W Enum 0
Loop_Test 404A Simulation mode Simulation mode is used to change the device's operating mode. OFF for normal measure operation. ON for analog output simulation. The value of analog output can be inserted in the page Simulation value. R/W Enum 0
Loop_Test_Value 404B Simulation value Current at the output when simulation is set to ON. (value between 3.58 and 21.7 mA) R/W Float 0
variable_array_index 404D R/W Index 4096
Name ID Label Description Type Access Class