Name ID Label Description Type Access Class
Max_Indicator_0 403B Max value S1 Shows the maximum process value of sensor 1. The value can be written to reset the indicator. R/W Float 2050
Min_Indicator_0 403C Min value S1 Shows the minimum process value of sensor 1. The value can be written to reset the indicator. R/W Float 2050
Value_0 401C Value Sensor 1 This parameter shows the measuring value of sensor 1. R Float 2050
Status_0 4038 Status sensor 1 Status sensor 1 - The status of sensor 1 is shown. R Unsigned 2051
Sensortype_1 4009 Sensor 2 type Allocation of sensor 2 sensor type using a selection list. R/W Enum 2048
Sensor_Connection_1 400A Sensor 2 connect. Allocation of connection mode (2-/3-wire) on resistance thermometers and resistance transmitters. R/W Enum 2048
RJ_Mode_1 4027 Cold junction S2 For TC input only. Selection of cold junction position. Internal: The temperature measured by the internal cold junction of the transmitter is used as compensation. External: The preset temperature is used for compensation. R/W Enum 2048
RJ_Fixed_Value_1 4028 External temp. S2 Fixed preset temperature. This is the temperature used for compensation when measuring using thermocouples. R/W Float 2048
Two_Wire_Comp_1 4029 2-wire comp. S2 Correction value for compensation for the cable resistance when using 2 wire RTDs. 0 Ohm to 30 Ohm can be set up. R/W Float 2048
Bias_1 402A Offset sensor 2 Additional calibration of the input signal in order to offset measurement deviations due to the installation or to compensate any sensor drift. An offset of -10 to +10 K (-18 F to 18 F) can be set up. R/W Float 2048