Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
Max_Indicator_0 | 403B | Max value S1 | Shows the maximum process value of sensor 1. The value can be written to reset the indicator. | R/W | Float | 2050 |
Min_Indicator_0 | 403C | Min value S1 | Shows the minimum process value of sensor 1. The value can be written to reset the indicator. | R/W | Float | 2050 |
Value_0 | 401C | Value Sensor 1 | This parameter shows the measuring value of sensor 1. | R | Float | 2050 |
Status_0 | 4038 | Status sensor 1 | Status sensor 1 - The status of sensor 1 is shown. | R | Unsigned | 2051 |
Sensortype_1 | 4009 | Sensor 2 type | Allocation of sensor 2 sensor type using a selection list. | R/W | Enum | 2048 |
Sensor_Connection_1 | 400A | Sensor 2 connect. | Allocation of connection mode (2-/3-wire) on resistance thermometers and resistance transmitters. | R/W | Enum | 2048 |
RJ_Mode_1 | 4027 | Cold junction S2 | For TC input only. Selection of cold junction position. Internal: The temperature measured by the internal cold junction of the transmitter is used as compensation. External: The preset temperature is used for compensation. | R/W | Enum | 2048 |
RJ_Fixed_Value_1 | 4028 | External temp. S2 | Fixed preset temperature. This is the temperature used for compensation when measuring using thermocouples. | R/W | Float | 2048 |
Two_Wire_Comp_1 | 4029 | 2-wire comp. S2 | Correction value for compensation for the cable resistance when using 2 wire RTDs. 0 Ohm to 30 Ohm can be set up. | R/W | Float | 2048 |
Bias_1 | 402A | Offset sensor 2 | Additional calibration of the input signal in order to offset measurement deviations due to the installation or to compensate any sensor drift. An offset of -10 to +10 K (-18 F to 18 F) can be set up. | R/W | Float | 2048 |
Name | ID | Label | Description | Type | Access | Class |