Name ID Label Description Type Access Class
Display_Mode 4034 Display It is possible to change the display mode. With this parameter you can select the displayed values and adjust the display duration. The corresponding value can be taken from the operating instructions. R/W Unsigned 2048
Diplay_PV_Text 4035 Diplay text In this parameter a text can be entered that appears in the display on PV indication. R/W PackedAscii 256
Sensortype_0 4006 Sensor type S1 Allocation of sensor 1 sensor type using a selection list. R/W Enum 2048
Sensor_Connection_0 4007 Sensor connect. S1 Allocation of connection mode (2-/3-/4-wire) on resistance thermometers and resistance transmitters. R/W Enum 2048
RJ_Mode_0 4022 Cold junction S1 For TC input only. Selection of cold junction position. Internal: The temperature measured by the internal cold junction of the transmitter is used as compensation. External: The preset temperature is used for compensation. R/W Enum 2048
RJ_Fixed_Value_0 4023 External temp. S1 Fixed preset temperature. This is the temperature used for compensation when measuring using thermocouples. R/W Float 2048
Two_Wire_Comp_0 4024 2-wire comp. S1 Correction value for compensation for the cable resistance when using 2 wire RTDs. 0 Ohm to 30 Ohm can be set up. R/W Float 2048
Bias_0 4025 Offset sensor 1 Additional calibration of the input signal in order to offset measurement deviations due to the installation or to compensate any sensor drift. An offset of -10 to +10 K (-18 F to 18 F) can be set up. R/W Float 2048
unit_0 4008 Measuring unit S1 Display of sensor 1 engineering units. R Enum 32
SV1_Serial_No 4026 Serial no. S1 Input of sensor 1 serial number. (12 characters). R/W PackedAscii 2048