Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
flow_digital_value | 4001 | FO1 | FO1 - actual value of output frequency. | R | Float | 514 |
flow_totalisator | 4000 | Tot - Totalized Flow (Totalizer), '>' means overflow of totalizer has occurred. | R | Float | 34 | |
flow_unit_selected | 4006 | Flow Unit | R | Enum | 256 | |
pulse_output_unit_selected | 4007 | Vol Unit | R | Enum | 256 | |
length_units | 4008 | Size Unit | Size Unit - Unit of the nominal diameter parameter. | R/W | Enum | 32 |
length_unit_selected | 4009 | Size Unit | R | Enum | 256 | |
us_conversion_code | 400A | gal/bbl | Gallons/barrel - Defines the gallons (US or Imperial) and the amount of gallons per barrel. | R/W | Enum | 32 |
flow_range1_value | 400B | Range 1 | Range 1 Value - Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. | R/W | Float | 32 |
flow_range2_value | 400C | Range 2 | Range 2 Value - Defines the operational endpoint for the second range in the dual range mode. | R/W | Float | 32 |
flow_range_switch | 400D | Dual Range | Dual Range - This controls the dual range mode which affects the analog output. | R/W | Enum | 32 |
Name | ID | Label | Description | Type | Access | Class |