Loading…
Name ID Label Description Type Access Class
Snsr0DisplayLowerTrimPoint 40B2 Conc Lower trim Lower Trim Point- Applied process input at which the last lower trim of the device variable was performed. R Float 0
Snsr0DisplayUpperTrimPoint 40B3 Conc Upper trim Upper Trim Point- Applied process input at which the last upper trim of the device variable was performed. R Float 0
Snsr0DisplayTrimSupport 40B4 Conc Trim support Trim Points Supported- Indicates the trim points that are supported by the device variable during a trim procedure. R Enum 0
Snsr0DisplayMinimumLTP 40B5 Conc Min lower trim Minimum Lower Trim Point- The lowest applied process value that can be used duirng a low trim procedure (ie, no value lower than this will be accepted by the instrument). R Float 0
Snsr0DisplayMaximumLTP 40B6 Conc Max lower trim Maximum Lower Trim Point- The highest applied process value that can be used duirng a low trim procedure (ie, no value higher than this will be accepted by the instrument). R Float 0
Snsr0DisplayMinimumUTP 40B7 Conc Min upper trim Minimum Upper Trim Point- The lowest applied process value that can be used duirng a high trim procedure (ie, no value lower than this will be accepted by the instrument). R Float 0
Snsr0DisplayMaximumUTP 40B8 Conc Max upper trim Maximum Upper Trim Point- The highest applied process value that can be used duirng a high trim procedure (ie, no value higher than this will be accepted by the instrument). R Float 0
Snsr0DisplayMinimumTrimDiff 40B9 Conc Min trim diff Minimum Trim Differential- The minimum acceptable difference between the upper and lower trim points. R Float 0
Snsr0CalibValue 40BB Snsr 1 Calib Conc Snsr 1 Calibration Concentration R/W Float 10
Snsr0CalibUnits 40BC Conc units Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Enum 8
Name ID Label Description Type Access Class