Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
transfer_function | 1F84 | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R | Enum | 32 |
upperRange_value | 00EA | PV URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
lowerRange_value | 00EB | PV LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
eeprom_select | 0FAB | EEPROM select | Electrically Erasable Read Only Memory Selection- Controls the data in: EEPROM Read Only Memory / Read Only Memory. | R/W | Enum | 4096 |
device_variable_code | 1047 | Device Variable | Index into Dynamic Variables Array- An index that identifies a Field Device Variable that is dynamic with respect to time, with no user input | R/W | Index | 4096 |
Name | ID | Label | Description | Type | Access | Class |