Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
temperatureMaximumUTP | 401B | Max upper trim | Maximum Upper Trim Point- The highest applied process value that can be used duirng a high trim procedure (ie, no value higher than this will be accepted by the instrument). | R | Float | 0 |
temperatureMinimumTrimDiff | 401C | Min trim diff | Minimum Trim Differential- The minimum acceptable difference between the upper and lower trim points. | R | Float | 0 |
temperatureSimulated | 401D | PV Simulate | Fixes PV on desired value. | W | Enum | 0 |
iout_type | 401F | Type | Analog output type | R/W | Enum | 64 |
iout_alarm_low_value | 4020 | Low alarm current | The value of low level alarm current in mAps (Min 3.5, Max 4.0) | R/W | Float | 64 |
iout_alarm_high_value | 4021 | High alarm current | The value of high level alarm current in mAps (Min 20.0, Max 23.0) | R/W | Float | 64 |
probe_type | 4026 | Probe Type | Probe type - is a type of sensor connected to input. | R/W | Enum | 0 |
number_of_wires | 4027 | Snsr conectn | Sensor Connection- Technique used to connect the sensor to the Field Device | R/W | Enum | 0 |
temperature_standart | 4029 | Temp std | The type of temperature Standard used in Fuiled Device to measure temperature. | R | Enum | 0 |
probe_connection | 402A | Probes Connect | The type of Probe Connection to the input of field device. | R | Enum | 0 |