Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
Pressure_Value | 4001 | PV | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention | R/W | Float | 10 |
Pressure_Units | 4000 | Press. unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R | Enum | 10 |
sensor_value | 401D | Pressure | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention | R | Float | 10 |
temperature_value | 401E | Temperature | Pressure module's measured temperature | R | Float | 10 |
sensor_units | 401F | Press. unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R/W | Enum | 8 |
temperature_units | 4020 | Temp. Unit | This is Temperature Units | R | Enum | 8 |
sensor_upper_limit | 400B | PV USL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 8 |
sensor_lower_limit | 400A | PV LSL | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 8 |
sensor_minimum_span | 400C | Min. Span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 8 |
sensor_damping_value | 4021 | PV Damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |