Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
dec_input_transfer_function | 400A | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R | Enum | 32 |
dec_input_upper_value | 400B | PV URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R | Float | 32 |
dec_input_lower_value | 400C | PV LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R | Float | 32 |
dec_sensor_serial_number | 400D | PV Snsr s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 2048 |
dec_log_request | 400E | Event log request | W | Enum | 4096 | |
dec_password | 400F | Set Password | The password is used to validate the command to enable or disable writes in the device. | W | ASCII | 2052 |
dec_write_enable | 4010 | Set Write Protect | Used to set the write protect mode. With Write Protect (On), variables cannot be written to the device and commands that cause actions to be performed in the device cannot occur. | W | Enum | 2052 |
x5200_bit_fire_status | 401F | Fire | Indicates (Y) if the device is in a fire alarm status. - analog output is at 20mA, fire alarm relay is actuated and LED is red. | R | Enum | 2051 |
x5200_bit_uv_alarm | 4020 | UV Alarm | Indicates (Y) if the UV detector is signaling an alarm. | R | Enum | 2051 |
x5200_bit_ir_alarm | 4021 | IR Alarm | Indicates (Y) if the IR detector is signaling an alarm. | R | Enum | 2051 |
Name | ID | Label | Description | Type | Access | Class |