Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
x5200_bit_auto_uv_oi_fault | 402C | Auto UV Oi Fault | Automatic UV Oi Fault. Check UV viewing window and Oi reflector plate cleanliness. | R | Enum | 2051 |
x5200_bit_auto_ir_oi_fault | 402D | Auto IR Oi Fault | Automatic IR Oi Fault. Check IR viewing window and Oi reflector plate cleanliness. | R | Enum | 2051 |
x5200_bit_uv_oi_cal_fault | 402E | UV Oi Cal Fault | UV Oi Calibration has detected a fault condition. | R | Enum | 2051 |
x5200_bit_ir_oi_cal_fault | 402F | IR Oi Cal Fault | IR Oi Calibration has detected a fault condition. | R | Enum | 2051 |
x5200_bit_temp_range_fault | 4030 | Temp Range Fault | Detector integral temperature out of range-Operating range: -40F to +167F (-40C to +75C). | R | Enum | 2051 |
x5200_bit_voltage_range_fault | 4031 | Voltage Fault | Supply voltage is out of range. Specified operating voltage is 18 to 30 Vdc. | R | Enum | 2051 |
x5200_bit_snsr_hdwr_fault | 4032 | Sensor Hdwr. Fault | Sensor hardware fault. -If fault clears 3 minutes after powerup check man oi test line not connected to DC- -Verify supply volt is within Operating range (18 to 30 Vdc) If fault does not clear, replace sensor module. | R | Enum | 2051 |
x5200_bit_man_oi_start_fault | 4033 | Manual Oi at Start | Manual Oi at Start. On power up a manual Oi was started. Check the external input wiring. | R | Enum | 2051 |
x5200_bit_hart_hdwr_fault | 4034 | HIB Hardware Fault | HART Interface Board hardware fault. If fault persists replace HIB. DEC PN 007308-005 | R | Enum | 2051 |
x5200_bit_internal_comm_fault | 4035 | Internal Com. Flt | Internal communication fault. If fault persists replace HART interface board and/or sensor module. | R | Enum | 2051 |
Name | ID | Label | Description | Type | Access | Class |