Name ID Label Description Type Access Class
x3302_bit_config_3 4040 Fault Relay NE/NDE Fault relay, normally energized(NE) or normally de-energized(NDE). R Enum 2051
x3302_bit_config_4 4041 Aux Relay L/NL AUX relay, latching(L) or non-latching(NL). R Enum 2051
x3302_bit_config_5 4042 Aux Relay NE/NDE AUX relay, normally energized(NE) or normally de-energized(NDE). R Enum 2051
x3302_bit_config_67 4043 Sensitivity Detector sensitivity setting: Very high, High, Medium, or Low. R Enum 2051
x3302_ir_oi_failures 4044 Consecutive Oi Fails Allowable number of consecutive Oi failures to produce a fault. Factory set to 3 (minutes). This is the time between fault occurrence and annunciation. R/W Unsigned 2051
x3302_temp_set_point 4045 Temp Setpoint Temperature at which heater begins operating. (-55C to+75C) R/W Unsigned 2051
x3302_htr_pwr 4046 Heater Power Actual heater power (0-100%). Heater prevents condensation and icing on the detector optics. R Unsigned 2051
x3302_htr_set_point 4047 Heater Setpoint Maximum amount of heater power allowed (in percent of full power, 0-100). R/W Unsigned 2051
x3302_response_time 4048 Response Time Fire alarm processing time in seconds. R Enum 2051
x3302_oi_fail_count 4049 Oi Fail Count Number of consecutive Oi failures counted (one passed Oi test resets the counter). R Unsigned 2051