名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
x3302_bit_warm_up | 4022 | Warm Up | Device is in the power-up time delay (warm-up) mode. Normal duration 30 seconds. | 读 | 枚举 | 2051 |
x3302_bit_fault_status | 4023 | Fault | Indicates (Y) if a fault condition exists.Go to (Device Info) and select (Status Info) to determine the nature of the fault. | 读 | 枚举 | 2051 |
x3302_bit_auto_oi_fault | 4024 | Automatic Oi Fault | Automatic Oi Fault. Check viewing windows and Oi reflector plate for cleanliness. | 读 | 枚举 | 2051 |
x3302_bit_man_oi_fault | 4025 | Manual Oi Fault | The detector has failed the last manual Oi test. | 读 | 枚举 | 2051 |
x3302_bit_oi_cal_fault | 4026 | Oi Calibrate Fault | An Oi calibration fault has occured. | 读 | 枚举 | 2051 |
x3302_bit_dim_detect_fault | 4027 | Diminish. Detect. Flt | Diminished Detection Fault. Excessive background IR radiation.Eliminate IR interference and/or re-aim/orient detector. | 读 | 枚举 | 2051 |
x3302_bit_detect_disable_fault | 4028 | Detect. Disable Flt | Flame detector function has been disabled! Check viewing windows for cleanliness and/or presence of excessive background IR signal. If uncorrectable replace sensor. | 读 | 枚举 | 2051 |
x3302_bit_temp_range_fault | 4029 | Temp Range Fault | Detector integral temperature out of range-Operating range: -40F to +167F (-40C to +75C). | 读 | 枚举 | 2051 |
x3302_bit_voltage_range_fault | 402A | Voltage Fault | Supply voltage is out of range. Specified operating voltage is 18 to 30 Vdc. | 读 | 枚举 | 2051 |
x3302_bit_snsr_hdwr_fault | 402B | Sensor Hdwr. Fault | Sensor hardware fault. -If fault clears 3 minutes after powerup check man oi test line not connected to DC- -Verify supply volt is within Operating range (18 to 30 Vdc) If fault does not clear, replace sensor module. | 读 | 枚举 | 2051 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |