Name ID Label Description Type Access Class
x2200_bit_config_1_2 404A Auto Oi Enabled Auto Oi Enabled. If (Y) then an Oi will be conducted periodically without manual input. R Enum 2051
x2200_bit_config_1_3 404B Fire Relay NL/L Fire relay, latching(L) or non-latching(NL). R Enum 2051
x2200_bit_config_1_4 404C Fault Relay NL/L Fault relay, latching(L) or non-latching(NL). R Enum 2051
x2200_bit_config_1_5 404D Aux Relay NL/L AUX relay, latching(L) or non-latching(NL). R Enum 2051
x2200_bit_config_1_7 404E Heater Disabled Heater Disabled. If (Y) then the optics heater is not enabled to prevent condensation and icing. R Enum 2051
x2200_bit_config_2_012 404F Aux Function Aux function: Pre Alarm, IR Alarm, UV Alarm, UV OR IR Alarm, UV AND IR Alarm. R Enum 2051
x2200_bit_config_2_34 4050 Aux IR Function Aux IR function: TDSA, Quick, or Both R Enum 2051
x2200_bit_config_2_5 4051 Aux Relay NE/NDE AUX relay, normally energized(NE) or normally de-energized(NDE). R Enum 2051
x2200_ir_oi_failures 4052 Consecutive IR Oi Fails Allowable number of consecutive IR Oi failures to produce a fault. Factory set to 3 (minutes). This is the time between fault occurrence and annunciation. R/W Unsigned 2051
x2200_uv_oi_failures 4053 Consecutive UV Oi Fails Allowable number of consecutive UV Oi failures to produce a fault. Factory set to 3 (minutes). This is the time between fault occurrence and annunciation. R/W Unsigned 2051
Name ID Label Description Type Access Class