Name ID Label Description Type Access Class
x2200_bit_auto_uv_oi_fault 402C Auto UV Oi Fault Automatic UV Oi Fault. Check UV viewing window and Oi reflector plate cleanliness. R Enum 2051
x2200_bit_auto_ir_oi_fault 402D Auto IR Oi Fault Automatic IR Oi Fault. Check IR viewing window and Oi reflector plate cleanliness. R Enum 2051
x2200_bit_uv_oi_cal_fault 402E UV Oi Cal Fault UV Oi Calibration has detected a fault condition. R Enum 2051
x2200_bit_ir_oi_cal_fault 402F IR Oi Cal Fault IR Oi Calibration has detected a fault condition. R Enum 2051
x2200_bit_temp_range_fault 4030 Temp Range Fault Detector integral temperature out of range-Operating range: -40F to +167F (-40C to +75C). R Enum 2051
x2200_bit_voltage_range_fault 4031 Voltage Fault Supply voltage is out of range. Specified operating voltage is 18 to 30 Vdc. R Enum 2051
x2200_bit_snsr_hdwr_fault 4032 Sensor Hdwr. Fault Sensor hardware fault. -If fault clears 3 minutes after powerup check man oi test line not connected to DC- -Verify supply volt is within Operating range (18 to 30 Vdc) If fault does not clear, replace sensor module. R Enum 2051
x2200_bit_man_oi_start_fault 4033 Manual Oi at Start Manual Oi at Start. On power up a manual Oi was started. Check the external input wiring. R Enum 2051
x2200_bit_hart_hdwr_fault 4034 HIB Hardware Fault HART Interface Board hardware fault. If fault persists replace HIB. DEC PN 007308-005 R Enum 2051
x2200_bit_internal_comm_fault 4035 Internal Com. Flt Internal communication fault. If fault persists replace HART interface board and/or sensor module. R Enum 2051