Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
greenLedturnoffTime | 4064 | Green LED turn off time | Green led will be turned off after specified time if configured in off mode value must be between 30 to 600 seconds | R/W | Unsigned | 8 |
beamblockfaulttime | 4065 | Beam block fault time | Time to activate the beam block fault since beam was blocked, value must be between 60 seconds to 21600 seconds, 6 hours | R/W | Unsigned | 8 |
FLASHCRC_RX | 4066 | RX flash CRC | R | Unsigned | 2048 | |
FLASHCRC_TX | 4067 | TX flash CRC | R | Unsigned | 2048 | |
dec_analog_alarm_code | 4074 | AO Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 66 |
dec_loop_flags | 4075 | Channel flags | Analog Channel Flags- Defines the characteristics of the Analog Channel | R | BitEnum | 64 |
device_status | 0097 | Device status | Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process | R | BitEnum | 131 |
units_code | 07E9 | R/W | Enum | 4096 | ||
transfer_function_code | 07EA | R/W | Enum | 4096 | ||
material_code | 07EC | R/W | Enum | 4096 | ||
Name | ID | Label | Description | Type | Access | Class |