Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
Level_Value | 4001 | Level | Instrument Primary Variable expressed in Engineering Units. Valid only if sensor. Calibration has been completed and accurate displacer and process fluid data have been entered in instrument memory | R | Float | 10 |
Level_Units | 4002 | Level Units | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R/W | Enum | 10 |
Level_Family | 4003 | Device family | Device Family- Indicates the family (i.e, pressure, temperature, flow, etc.) that the device variable belongs. | R | Enum | 2048 |
Level_Classification | 4004 | Class | Classification- Indicates the unit code expansion table used for a particular dynamic or device variable. | R/W | Enum | 0 |
Level_PDQ | 4005 | PDQ | Process Data Quality- Indicates the overall process data quality of the device variable value. | R | Enum | 10 |
Level_LS | 4006 | LS | Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). | R | Enum | 10 |
Level_Status | 4007 | Family status | Device Family Status- Indicates additional status information on a device variable for a specific device family. | R | BitEnum | 10 |
Level_USL | 4008 | USL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R/W | Float | 0 |
Level_LSL | 4009 | LSL | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R/W | Float | 0 |
Level_MinimumSpan | 400A | Min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R/W | Float | 0 |