Loading…
Name ID Label Description Type Access Class
flow_value 1F7C Flo Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention R Float 10
flow_units 1F7B Unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R/W Enum 8
sensor_upper_limit 403C USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
sensor_lower_limit 403D LSL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
sensor_minimum_span 403E Min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
sensor_damping_value 403F Damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 8
analog_value 4004 AO1 Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes R/W Float 66
analog_alarm_code 4040 AO Alrm typ Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R/W Enum 64
input_percent_range 4002 Flo % Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
input_transfer_function 4041 Xfer fnctn Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. R Enum 32
input_units 4042 Rnge unit Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value R Enum 4096
input_upper_value 4001 URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
input_lower_value 4000 LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
sensor_serial_number 401B Snsr s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R/W Unsigned 2048
frequency_value 4003 Vortex freq Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention R Float 10
frequency_units 4043 Unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Enum 8
total_totalizer 4005 Total totalizer Totalizer is not resetable directly. It can be forced while changing the unit R Float 16
daily_totalizer 4006 Daily totalizer Daily totalizer is resetable. Total totalizer will be unchanged at reset. R Float 16
totalizer_units 4060 Totalizer Unit Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value R Enum 16
totalizer_para 4061 Para totalzer R/W Unsigned 4096
k_factor_value 401C k-factor value R/W Float 2048
k_factor_unit 404B k-factor unit R/W Enum 8
puls_mode_factor 401D Pulse mode factor Pulse mode factor R/W Enum 32
sensor_type 401A Line of products Snsr model R Enum 2048
model_code 4019 Modelcode R PackedAscii 8
Name ID Label Description Type Access Class