Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
input_transfer_function | 4063 | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R | Enum | 32 |
input_upper_value | 4007 | max. Flowrate | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
input_lower_value | 4064 | min. Flowrate | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
sensor_serial_number | 4000 | PV Snsr s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R/W | Unsigned | 2048 |
low_flow_cut_off | 4001 | Low Flow Cutoff | The low flow is suppressing the indication resp. totalisation of 'wrong' liquid movements. The setting is posssible in the range of 0 - 10% referring to the full scale. | R/W | Float | 2048 |
flow_direction | 4002 | Flow Direction | At measurement in uni-directional direction flows will be indicated and added only in main flow direction. In bi-directional direction flow in both directions will be indicated and added. | R/W | Enum | 2048 |
detector_factor1 | 4003 | Detector Factor | Calibration constant detected and adjusted at the factory. Changing this value influences the measuring accuracy of the meter! This value should correspond to the transmitter constant on the sensor nameplate. | R/W | Float | 2048 |
pulse_value | 400B | Pulse output | The pulse value defines how many pulses per volume unit will be given. Max. output frequency 10 kHz. | R/W | Float | 2048 |
pulse_widthUnit | 4038 | Pulse width Unit | The time unit of the pulse length is ms (1/1000 second) | R/W | Enum | 2048 |
pulse_widthValue | 4039 | Pulse width | The pulse width defines the temporal length of a pulse. Max. 500 ms. | R/W | Float | 2048 |
Name | ID | Label | Description | Type | Access | Class |