Loading…
Name ID Label Description Type Access Class
coldTemperatureStatus 4015 Temp Dev Stat R BitEnum 2
coldTemperatureUSL 4016 Temp USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 0
coldTemperatureLSL 4017 Temp LSL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 0
coldTemperatureMinimumSpan 4018 Temp min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 0
coldTemperatureDampingValue 4019 Temp damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 0
coldTemperatureUpdatePeriod 401A Temp Update Period R Time 0
coldTemperatureSerialNumber 401B Temp snsr s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R Unsigned 0
coldTemperatureSimulated 401C Simulate W Enum 0
PV_TYPE 4026 PV TYPE PV TYPE - Making sure that the units for Sensor1 and Sensor2 are the same, when PV Type is the “DIFFERENCE_1_2” “DIFFERENCE_2_1” “MAXIMUM” “MINIMUM” “AVERAGE” type. R/W Enum 8
sensor1Type 4029 Sensor1 Type Sensor1 Type R/W Enum 8
Name ID Label Description Type Access Class