Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
rreset_changflg | 4022 | Reset Change Flag | R/W | Float | 4096 | |
sensor_value | 4025 | Pressure | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention | R | Float | 10 |
sensor_units | 4026 | Pressure Unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R/W | Enum | 8 |
sensor_upper_limit | 4027 | PV URL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 8 |
sensor_lower_limit | 4028 | PV LRL | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 8 |
sensor_minimum_span | 4029 | PV Min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 8 |
sensor_damping_value | 402A | PV Damping | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 8 |
analog_value | 4013 | Analog Output | Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes | R/W | Float | 66 |
analog_alarm_code | 4014 | AO Alarm Type | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 64 |
input_percent_range | 402B | PV % Range | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
input_transfer_function | 402C | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R/W | Enum | 32 |
input_range_units | 402D | PV rnge unit | Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value | R | Enum | 32 |
input_upper_value | 402E | URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
input_lower_value | 402F | LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
sensor_serial_number | 4030 | Sensor Serial Number | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 2048 |
sensor2_value | 4031 | Sensor Temp | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention | R | Float | 10 |
sensor2_units | 4000 | Temp Unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R/W | Enum | 8 |
cutoff_mode | 4032 | Cutoff Mode | R/W | Unsigned | 64 | |
dropout_point | 4011 | Dropout Point | R/W | Float | 64 | |
display_type | 4033 | Display Type | R/W | Unsigned | 64 | |
eu_lower_value | 4018 | EU LO | R/W | Float | 64 | |
eu_upper_value | 4019 | EU HI | R/W | Float | 64 | |
height | 4002 | Height | R/W | Float | 32 | |
out_lower_limit | 401A | Lo Limit | R/W | Float | 64 | |
out_upper_limit | 401B | Hi Limit | R/W | Float | 64 | |
type_code | 4001 | Measurement Type | R | Enum | 2048 | |
prom_id | 400C | PROM ID | R | ASCII | 2048 | |
set_output_value | 4034 | Set Output Value | R/W | Float | 4096 | |
conf_de_type | 4020 | DE Mode | R/W | Enum | 2048 | |
conf_bo_type | 4021 | B/O Direction | R/W | Enum | 2048 | |
service_password | 4035 | R/W | Integer | 4096 | ||
unique_device_type_code | 07ED | R/W | Enum | 4096 | ||
rosemount_model_code | 07F5 | R/W | Enum | 4096 | ||
rosemount_analytical_model_code | 07F6 | R/W | Enum | 4096 | ||
kayray_model_code | 07F7 | R/W | Enum | 4096 | ||
micro_motion_model_code | 07F8 | R/W | Enum | 4096 | ||
units_code | 07E9 | R/W | Enum | 4096 | ||
transfer_function_code | 07EA | R/W | Enum | 4096 | ||
material_code | 07EC | R/W | Enum | 4096 | ||
alarm_selection_code | 07EB | R/W | Enum | 4096 | ||
write_protect_code | 07EE | R/W | Enum | 4096 | ||
company_identification_code | 07EF | R/W | Enum | 4096 | ||
burst_mode_control_code | 07F0 | R/W | Enum | 4096 | ||
physical_signaling_codes | 07F1 | R/W | Enum | 4096 | ||
flag_assignment | 07F2 | R/W | Enum | 4096 | ||
operating_mode_code | 07F3 | R/W | Enum | 4096 | ||
analog_output_numbers_code | 07F4 | R/W | Enum | 4096 | ||
response_code | 0096 | Command Specific Response Code- Data that is returned in the Field Device response, that indicates the relative success of the Command sent in the Host request. This information may relate to the Data of the Host request or to the command itself. | R/W | Enum | 129 | |
comm_status | 0098 | Communications Error Summary- The Field Device has detected the following error condition while attempting to receive the Host request. Therefore the Command was not accepted, and the Host request caused no change to occur in the Field Device. | R/W | BitEnum | 131 | |
device_status | 0097 | Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process | R/W | BitEnum | 131 | |
Name | ID | Label | Description | Type | Access | Class |