Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
flow_minimum_span | 1F81 | PV Min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R/W | Float | 32 |
flow_range_units | 1F88 | PV rnge unit | Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value | R/W | Enum | 32 |
flow_upper_range_value | 1F85 | PV URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
flow_lower_range_value | 1F86 | PV LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
flow_damping_value | 1F87 | PV Damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 32 |
pulse_output_value | 1F73 | Puls outp | Pulse Output Value- scaled frequency output from 0-1000 Hz, linear with input. | R | Float | 514 |
net_total_value | 1F8A | Measure net totl | Net Total Value- Resettable totalizer value. Counts frequency output pulses while total control is turned on. | R | Float | 18 |
gross_total_value | 1F89 | Measure gross totl | Gross Total Value- Non-resettable totalizer value. Counts frequency output pulses while total control is turned on. This value will be reset to 0 when the pulse scaling, line size, or units are changed. | R | Float | 18 |
reverse_total_value | 1F8B | Measure reverse totl | Reverse Total Value- Non-resettable totalizer value. Counts frequency output pulses while total control is turned on and flow is in the reverse direction. This value will be reset to 0 when the pulse scaling, line size, or units are changed. | R | Float | 18 |
transfer_function | 1F84 | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R | Enum | 64 |
Name | ID | Label | Description | Type | Access | Class |