Loading…
Name ID Label Description Type Access Class
ds_do_calib_sim_clear 4042 Clear CALIB simulation R/W Enum 2048
ds_do_calib_sim_cont 4043 Continue CALIB simulation R/W Enum 2048
ds_process_alarm_status 4044 Proc. alarm status Proc. alarm status- Shows the Process alarm status, No alarm or Alarm. R Enum 2050
ds_process_alarm_lower_val 4045 Proc. alarm lower alarm value Proc. alarm lower alarm value- Lower limit of process alarm. Setting range is -5 to 105%, and Lower+hys < Upper-hys. R/W Float 2048
ds_process_alarm_upper_val 4046 Proc. alarm upper alarm value Proc. alarm upper alarm value- Upper limit of process alarm. Setting range is -5 to 105%, and Lower+hys < Upper-hys. R/W Float 2048
ds_process_alarm_hys 4047 Proc. alarm hysteresis(0 to 5) Proc. alarm hysteresis- Setting range is 0 to 5 % in 1 % increments. Hysteresis is effective at lower part of Upper alarm, and upper part of Lower alarm. R/W Float 2048
ds_scaled_da_trim_voltage 4048 250ohm load resistance voltage R/W Float 2048
ds_scaled_da_trim_zero 4049 250ohm load resistance voltage zero R/W Float 2048
ds_scaled_da_trim_gain 404A 250ohm load resistance voltage gain R/W Float 2048
ds_scv_trim_value 404B PV trim(-2.000 to 2.000) PV trim- PV trim value. Setting range is -2.000 to 2.000 MJ/m3. R/W Float 2048
Name ID Label Description Type Access Class