Name ID Label Description Type Access Class
sensor_upper_limit 4052 PV upper range limit PV upper range limit defines the maximum usable value for the PV upper range value. R Float 2050
Out_Range_Low 400D PV lower range value Valor da faixa inferior- Define o endpoint operacional do qual o valor analógico, e o ponto de )% da faixa de porcentagem são derivado. Além do valor da faixa inferior definir um endpoint operacional no qual o alarme associado com o valor analógico, e os alarmes associados com a representação de valor digital são derivados. R/W Float 34
Out_Range_High 400C PV upper range value Valor de faixa superior- Define o endpoint operacional do qual o valor analógico, e o ponto 100% da faixa de porcentagem são derivados. Além do que, o valor da faixa superior define um endpoint operacional no qual o alarme associado com o valor analógico, e os alarmes associados com a representação do valor digital são derivados. R/W Float 34
Out_Mode 402D Analog output Selection of standard operation 4..20 mA (small output signal by small process variables) or inverse operation 20..4 mA (small output signal on high process variables). R/W Enum 2048
Out_Damping 402E Filter time Input for filter, from measurement recording to output. (0 to 60 seconds) R/W Float 2048
Error_Mode 400E Fault condition Select the fault information on sensor fault. When a sensor defect is recognised the transmitter transmits the defined output value. R/W Enum 2048
Hi_Alarm_Output 4076 Failure output Defines the exact failure output value in case of high alarm between 21.6 mA and 23 mA. R/W Float 2048
Out_Of_Range_Alarm 4069 Over/Und.rangealarm On: In case of under- or overrange the transmitter will switch to alarm. Off: In case of under- or overrange the analog output freezes at 3.8 mA in underrange and at 20.5 mA in overrange. R/W Enum 2048
Loop_Test 404A Simulation mode Simulation mode is used to change the device's operating mode. OFF for normal measure operation. ON for analog output simulation. The value of analog output can be inserted in the page Simulation value. R/W Enum 2048
Loop_Test_Value 404B Simulation value Current at the output when simulation is set to ON. (value between 3.58 and 21.7 mA) R/W Float 2048
Name ID Label Description Type Access Class